3.5 MCSMAGNUMAddressSettings
TheMCSBMSGATEWAYisconnectedtotheMCSMAGNUMviaEthernet.TheBacnetDeviceIDandtheIP
addressoftheMCSMAGNUMmustbesetupproperlytoenablesuccessfulcommunicationsbetweentheMCS
BMSGATEWAYandtheMCSMAGNUM.
TheMCSMAGNUMBACNETDEVICEIDmustbeset
totheaddressspecifiedontheMCSBMSGatewayslabel
(ex.18111).
 
TheMCSMAGNUMBACNETDEVICEIDcanbeverifiedandchanged(withtheproperauthorizationcode)from
MCSMagnum’skeypadthekeypad/LCDofaliveunit.
TogetauthorizedonMagnumdothefollowing:
1. Press‘Menu’
2.
Using,,,orpositioncurserto‘Passwords’
3. Presskey.
4. Enter4digitpassword&press.
5. Press‘Menu’tomakenextselection.
ThefollowingstepswilldisplaytheBacnetDeviceID:
(tochangetheaddressyoufirstmustbeauthorized)
1.
PresstheMENUkeyandthenUsing,,,orpositioncursertoServToolsthenpresstheENTERkey.
2. thenUsing,,,orpositioncursertoBacnetDeviceIDthenpressEnter.
3. Use,,cursertochangethe
BacnetDeviceID.
4. SetyourdesiredaddressthenpressEnter.
5. Resetorcyclepowertothemagnumforthechangetotakeeffect.